BATTERY SELECTION, INSTALLATION, AND
The selected battery should consist of ce1lsand modules that can easily be changed out, since it is likely that individual ce1ls, modules, or the complete battery may have to be replaced during
TESTING METHODS AND TEST EQUIPMENT: Network and maintenance technicians shall conduct battery testing and maintenance routines based upon internal DC Cell Resistance testing. The DC Cell Resistance battery tests are conducted on a Three Times Per Year (4-month intervals) schedule to provide trended data and pass/fail data.
The IEEE Standards provide recommended practices and schedule for maintenance and testing, as well as guidance for determining when batteries should be replaced.
Measure the electrolyte temperature of 10% or more of the battery cells. At least once per year, the quarterly inspection will be augmented as follows: In the case of a lead-antimony battery, measure and record specific gravity and electrolyte temperature of all cells.
A typical Telecommunications Outside Plant cabinet is a non-controlled environment where temperatures can reach or exceed 140 Degrees Fahrenheit. Battery Float Voltage: The float voltage is that voltage, which provides the correct amount of battery charge current to maintain an optimal state of charge in the battery cell.